How do you update the system software without using the web interface?
In almost all situations, updating the system software can be quickly and easily accomplished using the controller’s web interface (Utilities > System Upgrade). However, in rare instances, the controller’s system software may become corrupted and it may be necessary to update the system software without the use of the web interface.
There are three ways to update the system software other than by using the web interface.
Use FTP and Telnet to write system software to the controller flash.
This method requires that GPL is active on the controller and that you have a working Ethernet connection. If the GPL Ethernet interface is operational, but the web interface is not available, perform the following procedure:
pc 907 = "/ROMDISK/bin/new_file.bin"
pc 906 = 2 ' To write a GPL system file.
or
pc 906 = 1 ' To write a FPGA program file.
Use the controller’s debugger to write system software to the flash via a serial line
This method requires a RS-232 serial port connection to the controller. You do not need an Ethernet connection to the controller or a GPL system running. You must obtain a system software file in S-record format from Precise customer support. These files are not normally distributed and typically have a “.mot” file extension instead of “.bin” (for the files that are loaded via the web interface).
dBUG MPC5200 MIDS2 4MB Version 1.36, Oct 17 2006 12:24:12
Copyright 1995-2003 Motorola, Inc. All Rights Reserved.
...
MBIST: ok
LOADER: System start aborted
Enter 'help' for help.
...
dBUG>
dBUG> dl
Escape to local host and send S-records now...
S-record download successful!
dBUG> store system
Use the controller’s debugger to write system software to the flash via Ethernet
This method requires a working RS-232 serial port connection to the controller, an Ethernet connection and a TFTP server on a remote host that can access the system software file. You do not need to have a GPL system running. You must obtain a system software file in S-record format from Precise customer support. These files are not normally distributed and typically have a “.mot” file extension instead of “.bin” (for the files that are loaded via the web interface).
dBUG MPC5200 MIDS2 4MB Version 1.36, Oct 17 2006 12:24:12
Copyright 1995-2003 Motorola, Inc. All Rights Reserved.
...
MBIST: ok
LOADER: System start aborted
Enter 'help' for help.
...
dBUG>
You will see output something like:dBUG> show
base: 16
baud: 115200
flow: off
port: PSC1
mac: 00:14:FF:00:00:EF
sn: 239
server: 192.168.53.98
client: 192.168.53.77
gateway: 192.168.53.1
netmask: 255.255.255.0
flags: 7
fpga: 0
partition: 256:1024:19072:12288:128
shift: 2
dBUG> set server new_ip_address
dBUG> set client new_ip_address
dBUG> set gateway new_ip_address
dBUG> set netmask new_ip_mask
dBUG> store
dBUG> dn new_file.mot
dBUG> store system